Example: 3 × 6mm² TPS cables = 3 × 78.54 = 235.6 mm². 235.6 ÷ 0.4 = minimum internal conduit area. Step 4: Select conduit size Use the internal diameter (ID) of Australian standard conduits (usually to AS/NZS 2053).

From the example above (589 mm² needed), you would select . 4. Practical Australian Reference Table (Common Cables) These are approximate maximums for short, straight runs (under 10m, minimal bends). For long runs or multiple 90° bends, drop one size. conduit size for cable australia

| Nominal Conduit Size (mm) | Approx. Internal Diameter (mm) | Approx. Internal Area (mm²) | Max 40% Fill Area (mm²) | |---------------------------|--------------------------------|----------------------------|--------------------------| | 16 | 12.5 | 123 | 49 | | 20 | 16.1 | 203 | 81 | | 25 | 20.7 | 336 | 134 | | 32 | 26.6 | 556 | 222 | | 40 | 33.4 | 876 | 350 | | 50 | 42.4 | 1,412 | 565 | Example: 3 × 6mm² TPS cables = 3 × 78